Siemens 6SL3120-2TE21-0AA3 Manual page 214

Booksize power units
Table of Contents

Advertisement

Cold plate
DC link capacitance
Active Line Module
Drive line-up, max.
Power factor
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit-current
SCCR
4)
Max. permissible heat sink
temperature
Max. ambient temperature
without derating
with derating
Weight
Derating must be applied due to the transfer of heat to the external heat sink. At a temperature of 40° C at the interface
1)
to the power unit, 80% derating occurs for 6SL3136-7TE28-0AAx and 70% for 6SL3136-7TE31-2AAx
The specified power ratings apply to the line voltage range from 380 V to 480 V.
2)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
3)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
4)
Module in the drive system.
Note
New systems with 80 kW and 120 kW Active Line Modules should ideally be designed with
120 kW Active Line Modules Liquid Cooled in order to avoid power derating.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
6SL3136-
21-6AAx
23-6AAx
7TE
μF
710
1410
μF
20000
20000
cosϕ
1
1
See Section Overcurrent protection using line fuses and circuit breakers
(Page 51)
kA
65
65
° C
70
73
° C
40
40
° C
55
55
kg
6.1
10.2
Line Modules Booksize
4.4 Active Line Modules with cold plate
25-5AAx
25-5AA3 +
28-0AAx
Active
Interface
Module
1880
1880
2820
20000
20000
20000
1
1
1
65
65
65
83
83
75
40
40
40
55
55
55
13.8
13.8
20.3
31-2AAx
3760
20000
1
65
80
40
55
20.4
213

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics s120

Table of Contents