Technical Data - Siemens 6SL3120-2TE21-0AA3 Manual

Booksize power units
Table of Contents

Advertisement

Note
If the cooling air requirement is not covered by the filtered fan, the components cannot
output their specified power.
The filters with filter fan must be regularly checked for dirt and cleaned if necessary.
4.3.7

Technical data

Table 4- 22
Technical data for Active Line Modules with external air cooling, part 1
External air cooling
Rated power
Infeed
Rated power (S1)
1)
Infeed power (S6 - 40 %)
1)
Peak infeed power
1)
Regenerative feedback
Continuous regenerative power
Peak regenerative power
Supply voltages
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Input currents
Rated input current:
for AC 400 V
Input current:
for AC 380 V / AC 480 V
for AC 400 V; S6 - 40 %
for AC 400 V; peak current
DC link currents
Rated DC link current:
for 600 V
DC link current:
for 600 V DC; for S6 - 40 %
for 600 V DC; peak current
Current carrying capacity
DC link busbars
Reinforced DC link busbars
24 V DC busbars
Electronics current drawn
at 24 V DC
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
6SL3131–
7TE21–6AAx
kW
16
kW (P
)
16
n
kW (P
)
21
s6
kW (P
)
35
max
kW
16
kW
35
V
3 AC 380 ... 480 ± 10 % (15 % < 1 min)
ACrms
Hz
47 ... 63 Hz
V
24 (20.4 ... 28.8)
DC
V
510 ... 720
DC
V
820 ± 2 %
DC
V
360 ± 2 %
DC
A
25
AC
A
26 / 21
AC
A
32
AC
A
54
AC
A
27
DC
A
35
DC
A
59
DC
A
100
DC
A
150
DC
A
20
DC
A
0,95
DC
4.3 Active Line Modules with external air cooling
7TE23–6AAx
7TE25–5AAx
36
55
36
55
47
71
70
91
36
55
70
91
55
84
58 /46
88 / 70
71
108
107
139
60
92
79
121
117
152
200
200
--
--
20
20
1,5
1,9
Line Modules Booksize
7TE25–5AA3
+ Active
Interface
Module
55
55
71
110
55
110
84
88 /70
108
168
92
121
176
200
--
20
1,9
193

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics s120