4.7.2.2

X1 line connection

Table 4- 51
X1: Line supply connection for Basic Line Modules 20 kW
For ring cable lugs without insulation
1)
Table 4- 52
X1: Line supply connection for Basic Line Modules 40 kW
For ring cable lugs without insulation
1)
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Terminal
Technical data
U1
Supply voltage:
3 AC 380 ... 480 V, 50 / 60 Hz
V1
Max. connectable cross-section: 16 mm
W1
Type: Screw terminal 7 (Page 755)
Tightening torque: 1.5 ... 1.7 Nm
PE connection
Threaded hole M5 / 3 Nm
Terminal
Technical data
U1
Supply voltage:
3 AC 380 ... 480 V, 50 / 60 Hz
V1
Max. connectable cross-section, 50 mm², end sleeves
W1
Tightening torque, min. 6 Nm
PE connection
Threaded hole M6 / 6 Nm
Line Modules Booksize
4.7 Basic Line Modules with cold plate
2
1
1)
253

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics s120

Table of Contents