Table 6- 46
Technical data Double Motor Modules (2 x 3 to 2 x 9 A) with 300% overload
Cold plate
Output current
Rated current (I
)
n
Base-load current (I
)
H
Intermittent duty current (I
S6
Peak current (I
)
max
Output voltage
DC-link current I
d max
DC-link voltage (up to 2000 m above sea level)
DC-link capacitance
Overvoltage trip
Undervoltage trip
1)
Electronics power supply
Electronics current drawn
at 24 VDC
Current carrying capacity
DC-link busbar
Reinforced DC-link busbars
24 V busbar
Unit rating
2)
Based on I
(600 VDC; 4 kHz)
n
Based on I
H
Total power loss
(including electronics losses, see Power loss
tables (Page 781))
Max. pulse frequency
without derating
with derating
Max. ambient temperature
without derating
with derating
Max. permissible heat sink temperature
Weight
Default for 400 V line systems; undervoltage trip threshold can be reduced by up to 80 V and is adjusted to the
1)
parameterized rated voltage
Rated power of a typical standard induction motor at 400 V 3 AC.
2)
466
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
6SL3126-
A
ACrms
A
) 40%
A
ACrms
A
ACrms
V
ACrms
A
DC
V
DC
μF
V
DC
V
DC
V
DC
A
DC
A
DC
A
DC
A
DC
kW
kW
W
kHz
kHz
° C
° C
° C
kg
2TE13-0AA4
2TE15-0AA4
2 x 3
2 x 5
2 x 2.6
2 x 4.3
2 x 3.5
2 x 6
2 x 9
2 x 15
0 ... 480
7,2
12
510 ... 720
110
220
820 ± 2 %
380
24 (20,4 ... 28,8)
0,9
0,9
100
100
150
150
20
20
2 x 1.6
2 x 2.7
2 x 1.4
2 x 2.3
91,6
126,6
4
16
40
55
77
77
4,5
4,5
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
2TE21-0AA4
2 x 9
2 x 7.7
2 x 10
2 x 27
22
220
0,9
100
150
20
2 x 4.8
2 x 4.1
181,6
77
4,5