Installer Setting - Static Pressure Setting - LG PREMTB10U Installation & Operation Manual

Lg programmable thermostat installation & operation
Hide thumbs Also See for PREMTB10U:
Table of Contents

Advertisement

Installer Setting - Static Pressure Setting

This function is applied to only duct type. Setting this in other cases will cause malfunction.
<Static Pressure Setting Table>
Pressure selection
01
V-H
02
F-H
03
V-L
04
F-L
INSTALLATION INSTRUCTION
Press
button for 4 seconds
1
to enter the installer setting
mode until timer segment
displays "01:01".
If pressing
2
moves to static pressure selection menu
as picture below.
Select static pressure by pressing
3
button.
(01:V-H, 02:F-H, 03:V-L, 04:F-L)
Function Code
Pressure
Press
button to save.
4
5
Pressing
button will exit settings mode.
❈ After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈ When exiting without pressing set button,
the manipulated value is not reflected.
Function
Zone state
Variable
Fixed
Variable
Fixed
button repeatedly, it
ESP standard value
High
High
Low
Low