Device Overview
Type Plate Data (from Type Plate on Previous Page)
Table 2-2
Type plate data
Specification
Input
Output
Temperature range
Degree of protection
Duty class
Cooling method
Weight
Explanation of the Option Short Codes
Table 2-3
Explanation of the option codes
Input options
L00
Radio interference suppression filter, limit class A1 (TN, TT systems)
L13
Main contactor (for currents < 800 A)
L22
Without line reactor in power range P < 500 kW (available soon)
L23
Line reactor u
L26
Main circuit-breaker (incl. fuses/circuit-breakers)
Output options
L08
Output filter
Input and output options
M70
EMC shield bus
M75
PE busbar
2-8
Value
3AC
Three-phase connection
380 – 480 V
Rated input voltage
239 A
Rated input current
3AC
Three-phase connection
0 – 480 V
Rated output voltage
210 A
Rated output current
0 -40 °C
Ambient temperature range within which the cabinet unit can
operate under 100 % load
IP20
Degree of protection
I
I: Duty class I to EN 60146-1-1 = 100 % (continuously)
(with the specified current values, the cabinet unit can operate
continuously under 100 % load)
AF
A: coolant: air
F: circulation method: forced cooling, drive unit (fan) in the
device
Weight of the cabinet unit
= 2 % for P > 500 kW
k
Explanation
Version
A
SINAMICS G150
Operating Manual