Siemens SINAMICS G150 Operating Manual page 226

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Technical Data
Table 12-19 Version C, 660 V – 690 V, part 3
Category
Order no. 6SL3710-
Rated motor output
Rated connection voltage
Rated input current
Rated output current
Base load current
Power loss
Cooling air requirement
Sound pressure level at 50/60
Hz
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
Protective earth connection
Fastening screw
Approx. weight (standard
version)
Dimensions (w x h x d)
Recommended protection
Cond./semi-cond. protection
Rated current
Size to DIN 43 620-1
12-18
Unit
1GH32-6CA0
kW
250
V
3 AC 660 V to 690 V ±10 % (-15 % < 1 min)
A
280
A
260
A
250
kW
5.0
m³/s
0.36
dB(A)
69/73
2
mm
2 x 95
2 x (4/0)
2
mm
2 x 240
2 x (600)
M12 (1 hole)
2
mm
2 x 95
2 x (4/0)
2
mm
2 x 185
2 x (500)
M12 (1 hole)
M12 (2 holes)
kg
300
mm
400 x 2000 x 600
3NE1 331-2
A
350
2
1GH33-3CA0
1GH34-1CA0
315
400
353
436
330
410
320
400
6.1
8.1
0.36
0.78
69/73
72/75
2 x 120
2 x 185
2 x (300)
2 x (500)
4 x 240
4 x 240
4 x (600)
4 x (600)
M12 (1 hole)
M12 (2 holes)
2 x 120
2 x 185
2 x (300)
2 x (500)
2 x 240
4 x 240
2 x (600)
4 x (600)
M12 (1 hole)
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
300
670
400 x 2000 x 600
600 x 2000 x 600
3NE1 334-2
3NE1 334-2
500
500
2
2
Operating Manual
11/03
SINAMICS G150

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents