Commissioning
Basic Commissioning: Entering the Basic Parameters
Basic commisioning
Back
p1070 Main setpoint
p1075 Additional setp.
p1080 Minimum speed
p1082 Maximum Speed
xxxxxxxxxxxxxxxxxxxxxxxxxxx
Help
F1
F2
F3
Basic commisioning
Back
p1082 Maximum Speed
p1120 RG.t_Ramp_Up
p1121 RG.t_Ramp-Down
p1135 RG.t_OFF3
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Help
F1
F2
F3
Final confirmation
ttt
Apply parameters permanently with OK
Help
F1
F2
F3
Motor identification
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Please switch on the drive to start
motor identification.
xxxxxxxxxxxxxxxxxxxxxxxxxxxx
Warning: The motor conducts current and
may cause the shaft to turn.
Help
Alarm
F1
F2
F3
Fig. 5-6
Basic commissioning – Further dialog screens, concluding with the motor ID
5-6
Entering the parameters for basic
commissioning
(03)r4055[00]
p1070 Main setpoint (03)r4055[00] means:
0%
0.000 min
-1
1500.000 min
-1
In the factory setting, the main setpoint (p1070) is
defaulted by analog input 0 (parameter r4055[00]) on
Change Continue
the customer terminal block (node address 03).
F4
F5
Press <F3> and <F2> to select the basic
parameters.
Press <F4> to change the values:
1500.000 min-1
The system displays a screen in which you can enter
20.00 s
the relevant values.
30.00 s
30.00 s
Press <F5> to continue.
Change Continue
F4
F5
Final confirmation
Confirm the basic parameters to save them.
Press <Back> to return to the previous dialog screen
Press <F5> to continue.
Back
OK
The entered basic parameters are permanently
stored and the necessary calculations for the control
are carried out.
F4
F5
Motor identification
You activate this function by pressing the LOCAL
key (wait until the LED in the LOCAL key lights up)
and then ON.
If you abort the motor ID function (<F4>), the motor
Cancel
control does not operate with the measured values
but with the motor characteristic values calculated
from the type plate data. The measurement
F4
F5
increases the control performance as deviations in
the electrical characteristic values are minimized on
account of deviations in the material properties and
manufacturing tolerances.
11/03
SINAMICS G150
Operating Manual