Monitoring, Functions, and Protective Functions
Setting Parameters
p1200
Flying restart operating mode
Setting the flying restart mode.
Values: 0: Flying restart is disabled
1: Flying restart is always active, start in direction of setpoint
2: Flying restart is active, with line ON, error, OFF2, start in direction of setpoint
3: Flying restart is active, with error, OFF2, start in direction of setpoint
4: Flying restart is always active, in direction of setpoint only
5: Flying restart is active, with line ON, error, OFF2, in direction of setpoint only
6: Flying restart is active, with error, OFF2, in direction of setpoint only
In operating modes 1 to 3, the search is carried out in both directions; in operating modes 4 to 6, the
search is carried out in the setpoint direction only.
p1202
Flying restart detection current
Defines the detection current for the flying restart function. The value refers to the rated motor current.
p1203
Flying restart search rate
This factor influences the rate at which the output frequency changes during the flying restart.
The higher the value, the longer the search time.
Settings
9.4
Protective Functions
(in preparation)
9-8
Setting range: 0 ... 6
Factory setting: 1
Setting range: 10 ... 400 %
Factory setting: 100 %
Setting range: 10 ... 400 %
Factory setting: 100 %
SINAMICS G150
Operating Manual
11/03