Siemens SINAMICS G150 Operating Manual page 94

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Operation
Settings: MENU – Settings – Control Settings
Save LOCAL mode (factory setting: yes)
• Yes : "LOCAL" or "REMOTE" operating mode is saved when the supply voltage
is switched off, and restored when the supply voltage is switched back on.
• No : "LOCAL" or "REMOTE" operating mode is not saved. "REMOTE" is active
when the supply voltage is switched back on.
LOCAL/REMOTE also during operation (factory setting: no)
• Yes : You can switch between LOCAL and REMOTE when the drive is switched
on (motor is running).
• No : Before the system switches to LOCAL, a check is carried out to determine
whether the drive is in the operational status. If so, the system does not switch
to LOCAL and outputs the message "Local not possible". Before the system
switches to REMOTE, the drive is switched off and the setpoint is set to 0.
6.2.3.3
ON / OFF Key
ON key : always active in LOCAL when the operator input inhibit is deactivated.
OFF key : in the factory setting, acts as OFF1 = ramp-down on the deceleration
ramp (p1121), when n = 0: voltage disconnection (only if a main contactor is
installed).
Settings: MENU – Settings – Control Settings
Red OFF key acts as : (factory setting: OFF1)
• OFF1 : Ramp-down on the deceleration ramp (p1121)
• OFF2 : Immediate pulse block, motor coasts to a standstill
• OFF3 : Ramp-down on the emergency stop ramp (p1135)
6-12
11/03
SINAMICS G150
Operating Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents