5. INSPECTION AND MAINTENANCE
Symptom
Overvoltage applied to
load when output turns
OFF
Load does not turn
OFF
(Triac output)
Time period fluctuates
when load is a CR
timer
(Triac output)
(b) Troubleshooting output circuits
Table 5.8 describes problems and corrective actions for output circuits.
Table 5.8 Troubleshooting Output Circuits
Cause
• If load is internally half-wave rectified
(some solenoids are like this)
A1SY22
Output module
Load
• With polarity (1), C is charged. With polarity (2),
the C charge voltage plus the power supply
voltage is applied across D1. Max. voltage is
approx. 2.2V.
• Leak current due to internal surge suppresor.
A1SY22
Output module
Leak current
A1SY22
Output module
• Connect a resistor between several tens k
and several hundreds k
(This method causes no problems with output
[1]
D1
terminals but can lead to deterioration or burn-
out of load internal diodes.)
[2]
• Connect a resistor across the load.
(If long wiring exists between the output card
and the load, leak currents also arise due to
Load
wiring capacity.)
• Drive a relay and use the relay contacts to drive
the CR timer.
(See note attached to Example 1, as some
timers are half-wave rectified internally.)
CR timer
Leak current
5 − 19
Corrective Action
across the load.
Resistor
Load
Resistor
Load
Resistor
Calculate resistor
CR timer
constant from load.