Toshiba H9 ASD Installation And Operation Manual page 103

Adjustable low voltage heavy duty industrial speed drive
Hide thumbs Also See for H9 ASD:
Table of Contents

Advertisement

F143
Input Terminal 4 (RES) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the drive to any change in the RES
terminal input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Input Terminal 5 – 12 Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the drive to any change in the 5 – 12
terminal inputs by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Input Terminal 13 – 20 Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the drive to any change in the 13 – 20
terminal inputs by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Input Terminal 17 (B12) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the B12 discrete input
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the functionality of the programmable B12 terminal to any
one of the user-selectable functions listed in
See the My Function Instruction Manual (P/N E6581335) for more
information on the function of this terminal.
Input Terminal 18 (B13) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the B13 discrete input
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable B13 terminal to any one
of the user-selectable functions listed in
See the My Function Instruction Manual (P/N E6581335) for more
information on the function of this terminal.
96
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Table 5 on pg.
234.
Table 5 on pg.
234.
Direct Access Number — F143
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F144
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F145
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F164
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Direct Access Number — F165
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No