Toshiba H9 ASD Installation And Operation Manual page 91

Adjustable low voltage heavy duty industrial speed drive
Hide thumbs Also See for H9 ASD:
Table of Contents

Advertisement

F020
eset Speed 3
Preset Speed 3
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0011 and is
identified as Preset Speed 3. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
eset Speed 4
Preset Speed 4
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0100 and is
identified as Preset Speed 4. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
Preset Speed 5
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0101 and is
identified as Preset Speed 5. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
Preset Speed 6
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0110 and is
identified as Preset Speed 6. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
Preset Speed 7
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0111 and is
identified as Preset Speed 7. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
84
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
F018
for more information on
F018
for more information on
F018
for more information on
F018
for more information on
F018
for more information on
Direct Access Number — F020
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Direct Access Number — F021
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Direct Access Number — F022
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Direct Access Number — F023
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Direct Access Number — F024
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
H9 ASD Installation and Operation Manual
F024

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

P9 asd

Table of Contents