F191

V/f 5-Point Setting Voltage 1

Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 1 establishes the output voltage level that is to
be associated with the frequency setting of
1).
The
F701
parameter setting will determine if the on-screen selection for this
parameter appears in the form of a Voltage (V) or as a Percentage (%) of the
ASD rating.
If using Voltage as a unit of measure and with no voltage correction
Disabled), the limit of the on-screen display value for this parameter is 200
volts for the 230-volt ASD and 400 volts for the 460-volt ASD.
The actual output voltage is scaled to the maximum EOI display values (e.g., a
100-volt EOI display corresponds to a 115-volt actual output for the 230-volt
ASD — ½ of the full display range).
If using % as a unit of measure and with no voltage correction
the ASD output voltage will be the percentage setting times 230 for the 230-
volt unit (or % times 460 volts for the 460-volt unit).
See
F190
for additional information on this setting.

V/f 5-Point Setting Frequency 2

Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 2 sets the frequency to be associated with
the voltage setting of parameter
See
F190
and
F191
for additional information on this setting.
102
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
F190
(V/f 5-Point Setting Frequency
F193
(V/f 5-Point Setting Voltage 2).
Direct Access Number — F191
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
(F307
(F307
Disabled),
Direct Access Number — F192
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz