Low-Current Detection Threshold; Low-Current Trip Threshold Time; Short Circuit Detection At Start; Over-Torque Trip - Toshiba H9 ASD Installation And Operation Manual

Adjustable low voltage heavy duty industrial speed drive
Hide thumbs Also See for H9 ASD:
Table of Contents

Advertisement

F611

Low-Current Detection Threshold

Program Protection Low-Current Settings
With the Low-Current Trip (F610) parameter is enabled, this function sets the
low-current trip threshold.
The threshold value is entered as a percentage of the maximum rating of the
drive.

Low-Current Trip Threshold Time

Program Protection Low-current Settings
With the Low-Current Trip (F610) parameter is enabled, this function sets the
time that the low-current condition must exist to cause a trip.

Short Circuit Detection At Start

Program Protection Special Protection Parameters
This parameter determines when the system will perform an Output Short
Circuit test.
Note:
Selection 3 is recommended for high-speed motor applications.
Because of the low impedance of high-speed motors the
standard-pulse setting may result in a motor malfunction.
Settings:
0 — Every Start (Standard Pulse)
1 — Power On or Reset (Standard Pulse)
2 — Every Start (Short Pulse)
3 — Power On or Reset (Short Pulse)

Over-Torque Trip

Program Protection Over-Torque Parameters
This parameter Enables/Disables the Over-Torque Tripping function.
When enabled, the ASD trips if an output torque value greater than the setting
of
F616
or
F617
exists for a time longer than the setting of F618.
When disabled, the ASD does not trip due to over-torque conditions.
Note:
A discrete output terminal may be activated when an over-torque
alarm occurs if so configured (see F130).
Settings:
0 — Disabled
1 — Enabled
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Direct Access Number — F611
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Direct Access Number — F612
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Units — Seconds
Direct Access Number — F613
Parameter Type — Selection List
Factory Default — Every Start (Standard
Pulse)
Changeable During Run — No
Direct Access Number — F615
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F615
185