Input
Function
Function Name
Command
0
NOP (No Operation)
1
ST
2
STN
3
AND
4
ANDN
5
OR
6
ORN
7
EQ
8
NE
9
GT
10
GE
11
LT
12
LE
13
ASUB
14
ON (Timer)
15
OFF (Timer)
16
COUNT1 (Timer)
17
COUNT2 (Timer)
18
HOLD
19
SET
20
RESET
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Table 11. My Function Operator Selections.
My Function Computational Selections
Disables the My Function feature.
Execute data read/transfer.
Execute inverted data read/transfer.
Logical product of A AND B.
Logical product of A AND B.
Logical sum of A OR B.
Logical sum of A OR B.
Compares data — Outputs 1 if Equal; 0 if not Equal.
Compares data — Outputs 0 if Equal; 1 if not Equal.
Compares data — Outputs 1 if A>B; 0 if AB.
Compares data — Outputs 1 if AB; 0 if AB.
Compares data — Outputs 1 if AB; 0 if AB.
Compares data — Outputs 1 if AB; 0 if A>B.
Outputs absolute difference between A and B — |A–B|
Enables the On response time delay settings of My Function Time Data 1 – 5
(F928
– F932) for My Function Data.
Enables the Off response time delay settings of My Function Time Data 1 – 5
(F928
– F932) for My Function Data.
Outputs a 1 upon reaching the pulse count setting of F933.
Outputs a 1 upon reaching the pulse count setting of F934.
Outputs the peak output value since powering up or since the last reset.
Sets data.
Resets data.
Function Description