6.3.5

Copying GUD to NCU

If you have expanded the GUD tags offline in the TIA Portal, you must copy the changed
DEF files with SINUMERIK Operate back to the NCU.
The DEF files of the GUD database used in the TIA Portal must match the DEF files in the
NC so that the WinCC RT Advanced Runtime can correctly access the GUD tags.
Procedure
To copy the GUD from the configuration PC to the NCU, proceed as follows:
1. On the configuration PC, copy the DEF files from the project folder to a USB flash drive.
The DEF files are located in the following directory:
<Project directory>\AdditionalFiles\HMI\Sinumerik\Userdata\
Example:
C:\Users\Admin\Documents\Automation\My_Project\AdditionalFiles\HMI\Sinumerik\Userd
ata\
2. In the SINUMERIK Operate user interface, in the operating area "Commissioning >
System data > NC data", copy the files from the USB flash drive into the "Definitions"
directory.
3. Activate the files using "Define and activate user files (GUD)".
SINUMERIK Integrate Create MyHMI / WinCC V13 SP1
Configuration Manual, 11/2014
Configuring variables
6.3 Configuring GUD tags
87