9.3

When Using the Module on the Remote I/O Network

This section describes the system configuration and program examples of when the CT input module is used on a
remote I/O network.
For details on the MELSECNET/H remote I/O network, refer to the following.
Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network)
(1) System configuration
Remote master station
(Station No.0)
(2) Programming condition
Digital output values are read in the following conditions.
• Used channel: CH1 to CH3
• Input range: Factory default range 0 to 5AAC
• Digital conversion method in CH1: Sampling processing
• Digital conversion method in CH2: Count average processing (50 times)
• Digital conversion method in CH3: Primary delay filter (Time constant: 100ms)
• If an error occurs in the module, an error code is displayed in BCD notation
Remote I/O station
(Station No.1)
QJ71LP21-25 (XY0 to XY1F)
QX10 (X20 to X2F)
QY10 (Y30 to Y3F)
Network No.1
CHAPTER 9 PROGRAMMING
CT input module (X/Y1000 to X/Y100F)
QJ72LP25-25
9
165