(23)Dropout status flag (Un\G161)
The setting status of the dropout function can be checked for each channel.
For details on the dropout function, refer to the following.
• Dropout Function (
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
0
0
b8 to b15 are fixed to "0".
(a) Dropout status flag (Un\G161) status
• When the dropout function is enabled, Dropout enabled (1) is stored in Dropout status flag (Un\G161).
• When the dropout function is disabled, Dropout disabled (0) is stored in Dropout status flag (Un\G161).
(24)CH Dropout value (Un\G162 to Un\G169)
Set the digital output value which is dropped out for each channel.
For details on the dropout function, refer to the following.
• Dropout Function (
(a) Setting range
• Setting range: 1 to 10000
• When the value after digital conversion is the dropout value or less, 0 is stored in CH Digital output value
(Un\G11 to Un\G18).
(b) Enabling the setting
Turn on then off Operating condition setting request (Y9) to enable the setting.
(c) Default value
All channels are set to 50.
Page 47, Section 4.8)
0
0
0
0
0
0
CH8 CH7 CH6 CH5
Page 47, Section 4.8)
CHAPTER 6 BUFFER MEMORY
b4
b3
b2
b1
b0
CH4
CH3
CH2
CH1
0: Dropout disabled
1: Dropout enabled