4.8

Dropout Function

When an input current is around 0A, a CT's conversion accuracy is low. To avoid digital output of such an unstable CT
input value, digital output values within the set value can be dropped to 0 forcibly.
(1) Operation of the dropout function
When the value in CH Digital output value (Un\G11 to Un\G18) is equal to or less than the set value in CH
Dropout value (Un\G162 to Un\G169) in advance, 0 is stored in CH Digital output value (Un\G11 to Un\G18).
(2) Setting procedure
1.
Set Enable (0) to Conversion enable/disable setting (Un\G0).
2.
Set Enable (0) to Dropout detection setting (Un\G160).
3.
Set values to CH Dropout value (Un\G162 to Un\G169).
CH
Dropout value (Un\G162 to Un\G169)
4.
Turn on then off Operating condition setting request (Y9).
Remark
To check whether the dropout function is enabled or disabled, refer to the following.
• Dropout status flag (Un\G161) (
Item
Page 119, Section 6.2 (23))
CHAPTER 4 FUNCTIONS
Setting range
1 to 10000
47