10.7
When a User Range Is Used and Parameters Are Set
Using the Configuration Function (with Another System)
(1) Stopping operation
196
1.
Open the "Device/Buffer Memory Batch Monitor"
window.
[Online]
[Monitor]
Batch]
2.
Enter and display the buffer memory address of
Conversion enable/disable setting (Un\G0).
3.
Set Conversion enable/disable setting (Un\G0) to
Disable (1) for all channels.
4.
Turn on Operating condition setting request (Y9).
5.
Confirm that the digital conversion has stopped
with Conversion completed flag (Un\G10).
6.
After checking Conversion completed flag (Un\G10),
check that Operating condition setting completed
flag (X9) turns off, then turn off Operating condition
setting request (Y9).
[Device/Buffer Memory