High-Speed Counter [C] (FX
High-speed counter only available in DC input type main units.
4.7.1

Types and device numbers of high-speed counters

1. Types of high-speed counters
The main unit has built-in 32-bit high-speed bi-directional counters (1-phase 1-count, 1-phase 2-count and 2-phase 2-
count). These high-speed counters are classified into hardware type or software type according to the counting
method. Some high-speed counters are capable of using an external reset input terminal and an external start input
terminal (for counting start).
2. Classification of high-speed counters according to counting method
• Hardware counters:
• Software counters:
3. Types of high-speed counters and input signal forms
The table below shows the types (1-phase 1-count, 1-phase 2-count and 2-phase 2-count) and input signals
(waveforms) of high-speed counters.
1-phase
1-count input
1-phase
2-count input
1 edge
count
2-phase
2-count
input
4 edge
count
4. Cautions on counterpart equipment connected to high-speed counter inputs
General-purpose inputs X000 to X007 are used for high-speed counter inputs. An encoder
method shown in the table below can be connected depending on the connected terminal.
Encoders adopting the voltage output method and absolute encoders cannot be connected to high-speed counter
inputs.
Output method of encoder which can be directly connected to input
terminal in main unit
Output method of encoder which can be directly connected to input
terminal in FX
-4HSX-ADP
3U
*1.
A rotary encoder adopting the output method shown above may not operate correctly depending on the
electrical compatibility. Check the specifications before connecting an encoder.
/FX
3U
3UC
These types of counters execute counting by hardware, but may be switched to software
counters depending on the operating condition.
These types of counters execute counting as CPU interrupt processing.
It is necessary to use each software counter within both limitations of maximum response
frequency and total frequency.
→ For the limitation of response frequency depending on the total frequency,
Input signal form
UP/DOWN
+1
+1
+1
UP
DOWN
A phase
A phase
+1
+1
B phase
B phase
Up-counting
+1
+1 +1 +1 +1
A phase
A phase
B phase
B phase
+1 +1 +1 +1
Up-counting
→ For the wiring, refer to the Hardware Edition of the main unit.

4.7 High-Speed Counter [C] (FX3U/FX3UC PLC)

PLC)
→ For the condition handled as software counters,
Down-count or up-count is specified by
turning on or off M8235 to M8245.
ON: Down-counting
OFF: Up-counting
A counter executes up-count or down-
count as shown on the left.
The counting direction can be checked
−1
−1
−1
with M8246 to M8250.
ON: Down-counting
OFF: Up-counting
−1
−1
A counter automatically executes up-
count or down-count
Down-counting
changes in the input status of the A/B
phase as shown on the left.
−1
−1 −1 −1 −1
The counting direction can be checked
with M8251 to M8255.
ON: Down-counting
OFF: Up-counting
−1 −1 −1 −1
Down-counting
Open collector transistor output method compatible with 24V DC
Differential line driver output method
(output voltage: 5V DC or less)
4 Devices in Detail
refer to Subsection 4.7.9.
refer to Subsection 4.7.10.
Counting direction