2. LDI instruction (initial logical operation, NC contact type)
Circuit program
LDIinstruction
X000
Bus line
Timing chart
X000
ON
Y000
*1
3. Indexing
Devices used in LD and LDI instructions allow indexing with index registers (V and Z).
(State relays (S), special auxiliary relays (M), 32-bit counters (C), and "D .b" cannot be indexed.)
Circuit program
X000V0
*1.
This function is supported only in FX
4. Bit specification of data register (D)
A bit in data register (D) can be specified as a device used in LD and LDI instructions.
Circuit program
D0.3
*1.
This function is supported only in FX
Errors
• When an I/O number used in LD or LDI instruction does not exist due to indexing, M8316 (Non-existing I/O
specification error) turns ON.
• When the device number of a device (M, T or C) other than I/O used in LD or LDI instruction does not exist due to
indexing, an operation error (error code: 6706) occurs.
182
Y000
ON
ON
ON
List program
0000
0003
Y000
/FX
3U
List program
0000
0003
Y000
/FX
3U
List program
0000
LDI
X000
0001
OUT
Y000
V0 to V7 and Z0 to Z7 are available in indexing.
When used devices are inputs (X) and outputs
(Y), values of index registers (V and Z) are
converted into octal numbers, and then added.
LD
X000V0
Example: When the value of V0 is 10, LD contact
OUT
Y000
PLCs.
3UC
When specifying a bit in data register, input "."
after a data register (D) number, and then input a
bit number (0 to F) consecutively.
Only 16-bit data registers are available.
LD
D0.3
Specify a bit number as "0, 1, 2, ... 9, A, B, ... F"
OUT
Y000
from the least significant bit.
Example: In the example shown on the left, LD
PLCs.
3UC
7 Basic Instruction
Connection to bus line
is set to ON (becomes conductive) or
OFF (becomes non-conductive) by
X012.
contact
is
set
to
ON
conductive) or OFF (becomes non-
conductive) by bit 3 of D0.
7.1 LD, LDI