15.5.1

How to select a seven-segment display unit

When selecting a seven-segment display unit based on its electrical characteristics, refer to the manual below:
1. Points to be checked for the seven-segment specifications
1)
The input voltage and current characteristics of the data input and strobe signal satisfy the output specifications of
the PLC.
- The input signal voltage (Lo) is approximately 1.5 V or less
- The input voltage is from 5V DC to 30V DC
2)
The seven-segment display unit has the BCD decoding and latch functions
15.5.2

How to select parameter "n" based on seven-segment display specifications

The value set to the parameter "n" varies depending on the signal logic of the seven-segment display. Select "n" as
described below.
The check column is provided at the bottom of the table. Check a corresponding type of logic (positive or negative),
and utilize it for parameter setting.
1. Role of the parameter "n"
The parameter "n" should be determined according to the data input logic (positive or negative) of the seven-segment
display unit, the logic (positive or negative) of the strobe signal and the number of sets of 4 digits to be controlled (1 or
2).
2. Checking the output logic of the PLC
Transistor outputs in PLCs are classified into the sink output type and source output type. The table below shows the
specifications for each type.
Logic
Output type
Output circuit
Description
Check
438
Negative logic
Sink output (− common)
Pull-up
resistor
Y000
LOW
COM1
Because transistor output (sink) is provided, the output
becomes low level (0 V) when the internal logic is "1 (ON
output)". This is called "negative logic."
15 External FX I/O Device – FNC 70 to FNC 79
15.5 FNC 74 – SEGL / Seven Segment With Latch
→ For the wiring, refer to the Hardware Edition of the PLC used.
Logic 1
ON
Pull-
down
resistor
PLC
Because transistor output (source) is provided, the output
becomes high level (V+) when the internal logic is "1 (ON
output)". This is called "positive logic."
Positive logic
Source output (+ common)
V+
+V0
ON
HIGH
Logic 1
Y000
PLC