Mitsubishi Electric FX3G SERIES Programming Manual page 343

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Input terminal
Input signal (X)
Filter time
REF instruction (executed)
END instruction (input) processing
Input refresh
REF instruction + END processing
Only END processing
Cautions
1. Setting the number of refreshed points "n"
Set a multiple of 8 such as "K8 (H8), K16 (H10) ... K256 (H100)". Any other numeric value causes an error.
2. Setting the head device number (D)
Make sure that the least significant digit number is "0" such as "X000, X010, X020 ..."or " Y000, Y010, Y020 ..."
Program examples
1. When refreshing inputs
Only X010 to X017 (8 points in total) are refreshed.
X000
FNC 50
REF
2. When refreshing outputs
Y000 to Y007, Y010 to Y017 and Y020 to Y027 (24 points in total) are refreshed.
X001
FNC 50
REF
5ms
10ms
D
n
X010
K 8
D
n
Y000
K 24
13 High-Speed Processing – FNC 50 to FNC 59
13.1 FNC 50 – REF / Refresh
Does not turn ON.
20ms
ON
10ms
10ms
ON
ON
Improved response
delay time
11
12
13
14
15
16
17
18
19
20
341

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u seriesFx3uc series

Table of Contents