Start-up and control with I/O
What this chapter contains
The chapter instructs how to:
• do the start-up
• start, stop, change the direction of rotation and adjust the speed of the motor
through the I/O interface.
Using the control panel to do these tasks is explained briefly in this chapter. For
details on how to use the control panel, please refer to chapter
on page 43.
How to start up the drive
Before you start, ensure that you have the motor nameplate data on hand.
The start-up may only be carried out by a qualified electrician.
The safety instructions given in chapter
procedure.
Check the installation. See the checklist in chapter
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if there is a risk of damage in case of incorrect direction of
rotation.
Apply input power.
The panel goes to the Output mode.
Select the application macro (parameter 9902).
The default value 1 (ABB STANDARD) is suitable in most cases.
The general parameter setting procedure in the Short Parameter mode is
described below. You find more detailed instructions on setting parameters
on page 51.
The general parameter setting procedure in the Short Parameter mode:
1. To go to the Main menu, press
otherwise press
2. Press keys
POWER-UP
ENTRY OF START-UP DATA
if the bottom line shows OUTPUT;
repeatedly until you see MENU at the bottom.
/
until you see "PAr S" in the display.
SAFETY
Safety
must be followed during the start-up
Installation
Control panel
checklist.
00
LOC
.
OUTPUT
9902
LOC
PAR
rEF
LOC
MENU
PAr S
LOC
MENU
Start-up and control with I/O
37
starting
Hz
FWD
s
FWD
FWD
FWD