Hand/Auto macro

This macro can be used when switching between two external control devices is
needed. To enable the macro, set the value of parameter
For the parameter default values, see section
on page 63. If you use other than the default connections presented below, see
section
Note: Parameter
Default I/O connections
1)
In Hand mode, the frequency reference comes
from the integrated potentiometer.
I/O terminals
on page 32.
2108
START INHIBIT must remain in the default setting 0 (OFF).
X1A
1
SCR
2
AI
3
GND
2)
4
+24V
5
GND
6
DCOM
7
DI1
8
DI2
9
DI3
10
DI4
11
DI5
X1B
12
COM
13
NC
14
NO
Default values with different macros
Signal cable shield (screen)
Frequency reference (Auto): 4...20 mA
Analog input circuit common
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1) (Hand)
Forward (0) / Reverse (1) (Hand)
Hand (0) / Auto (1) control selection
Forward (0) / Reverse (1) (Auto)
Stop (0) / Start (1) (Auto)
Relay output
No fault [Fault (-1)]
2)
360 degree grounding under a clamp.
9902
to 5 (HAND/AUTO).
1)
Application macros
61