ABB ACS150 User Manual page 82

Table of Contents

Advertisement

82
Index Name/Selection
2106
DC CURR REF
0...100%
2107
DC BRAKE TIME
0.0...250.0 s
2108
START INHIBIT
0 = OFF
1 = ON
2109
EM STOP SEL
0 = NOT SEL
1 = DI1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
-1 = DI1(INV)
-2 = DI2(INV)
-3 = DI3(INV)
-4 = DI4(INV)
-5 = DI5(INV)
2110
TORQ BOOST CURR Defines the maximum supplied current during torque boost. See parameter
15...300%
Actual signals and parameters
Description
Defines the DC braking current. See parameter
Value in percent of the motor nominal current (parameter
CURR)
Defines the DC braking time.
Time
Enables the start inhibit function. Drive start is inhibited if
- fault is reset.
- Run Enable signal activates while the start command is active. See
parameter
1601
RUN ENABLE.
- control mode changes from local to remote.
- external control mode switches from EXT1 to EXT2 or from EXT2 to EXT1.
Disabled
Enabled
Selects the source for the external emergency stop command.
The drive cannot be restarted before the emergency stop command is reset.
Note: The installation must include emergency stop devices and any other
safety equipment that may be needed. Pressing STOP on the drive's control
panel does NOT
- generate an emergency stop of the motor.
- separate the drive from dangerous potential.
Emergency stop function is not selected.
Digital input DI1. 1 = stop along the emergency stop ramp. See parameter
2208
EM DEC TIME. 0 = emergency stop command reset.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Inverted digital input DI. 0 = stop along the emergency stop ramp. See
parameter
2208
EM DEC TIME. 1 = emergency stop command reset
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
2101
START FUNCTION.
Value in percent
2104
DC HOLD CTL.
9906
MOTOR NOM
30
0
0 = OFF
0 = NOT SEL
100