Motor Potentiometer macro

This macro provides a cost-effective interface for PLCs that vary the speed of the
drive using only digital signals. To enable the macro, set the value of parameter
to 4 (MOTOR POT).
For the parameter default values, see section
on page 63. If you use other than the default connections presented below, see
section
Default I/O connections
1)
If DI3 and DI4 are both active or inactive, the
frequency reference is unchanged.
The existing frequency reference is stored
during stop and power down.
Application macros
I/O terminals
on page 32.
X1A
1
SCR
2
AI
3
GND
4
+24V
5
GND
6
DCOM
7
DI1
8
DI2
9
DI3
10
DI4
11
DI5
X1B
12
COM
13
NC
14
NO
Default values with different macros
Signal cable shield (screen)
Not in use by default: 0...20 mA
Analog input circuit common
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Frequency reference up
Frequency reference down
Constant speed 1: parameter
Relay output
No fault [Fault (-1)]
1)
1)
1202
9902