Cooling air flow requirements
The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O not in use) and maximum load (all digital
inputs in the on state and the fan in use). The total heat dissipation is the sum of the
heat dissipation in the main and control circuits.
Type
ACS150-
x = E/U
Rated I
1-phase U
= 200...240 V (200, 208, 220, 230, 240 V)
N
01x-02A4-2
01x-04A7-2
01x-06A7-2
01x-07A5-2
01x-09A8-2
3-phase U
= 200...240 V (200, 208, 220, 230, 240 V)
N
03x-02A4-2
03x-03A5-2
03x-04A7-2
03x-06A7-2
03x-07A5-2
03x-09A8-2
3-phase U
= 380...480 V (380, 400, 415, 440, 460, 480 V)
N
03x-01A2-4
03x-01A9-4
03x-02A4-4
03x-03A3-4
03x-04A1-4
03x-05A6-4
03x-07A3-4
03x-08A8-4
Heat dissipation
Main circuit
and I
1N
2N
W
BTU/Hr
W
25
85
6.3
46
157
9.6
71
242
9.6
73
249
10.6
96
328
10.6
19
65
6.3
31
106
6.3
38
130
9.6
60
205
9.6
62
212
9.6
83
283
10.6
11
38
6.7
16
55
6.7
21
72
10.0
31
106
10.0
40
137
10.0
61
208
10.0
74
253
14.3
94
321
14.3
Control circuit
Min
Max
BTU/Hr
W
BTU/Hr
22
12.3
33
16.0
33
16.0
36
17.1
36
17.1
22
12.3
22
12.3
33
16.0
33
16.0
33
16.0
36
17.1
23
13.3
23
13.3
34
17.6
34
17.6
34
17.6
34
17.6
49
21.5
49
21.5
111
Air flow
3
3
m
/h
ft
/min
42
-
-
55
24
14
55
24
14
58
21
12
58
21
12
42
-
-
42
-
-
55
24
14
55
24
14
55
21
12
58
21
12
45
-
-
45
-
-
60
13
8
60
13
8
60
13
8
60
19
11
73
24
14
73
24
14
00353783.xls E