66

20 LIMITS

2008
MAXIMUM FREQ
0.0...500.0 Hz

21 START/STOP

2102
STOP FUNCTION
1 = COAST
2 = RAMP

22 ACCEL/DECEL

2202
ACCELER TIME 1
0.0...1800.0 s
2203
DECELER TIME 1
0.0...1800.0 s
Actual signals and parameters
Maximum frequency
Defines the maximum limit for the drive output frequency.
f
2008
0
-(2008)
Maximum frequency
Stop mode of the motor
Selects the motor stop function.
Stop by cutting off the motor power supply. The motor coasts to a stop.
Stop along a linear ramp. See parameter group
Acceleration and deceleration times
Defines the acceleration time 1 i.e. the time required for the speed to change
from zero to the speed defined by parameter
- If the speed reference increases faster than the set acceleration rate, the
motor speed will follow the acceleration rate.
- If the speed reference increases slower than the set acceleration rate, the
motor speed will follow the reference signal.
- If the acceleration time is set too short, the drive will automatically prolong
the acceleration in order not to exceed the drive operating limits.
Time
Defines the deceleration time 1 i.e. the time required for the speed to change
from the value defined by parameter
- If the speed reference decreases slower than the set deceleration rate, the
motor speed will follow the reference signal.
- If the reference changes faster than the set deceleration rate, the motor
speed will follow the deceleration rate.
- If the deceleration time is set too short, the drive will automatically prolong
the deceleration in order not to exceed drive operating limits.
If a short deceleration time is needed for a high inertia application, the drive
should be equipped a brake resistor.
Time
Allowed frequency range
22
ACCEL/DECEL.
2008
MAXIMUM FREQ.
2008
MAXIMUM FREQ to zero.
Eur: 50 /
US: 60
t
1 = COAST
5
5