Configuring Using Vtrin
Table 2. Current Data Collection - Fields and Description (Continued)
Field name
Enable Redundant Data
Collection
Frequency
Deadband
24
For OPC UA: Denotes the OPC UA path for the tag to subscribe data.
The syntax for OPC UA path is:
opc.tcp://nodename:port/progid//ItemId;namespace=name
For example:
opc.tcp://fi8-
main:4841///Variable.SYS_CPU0_Time;UaNamespace=http://fi.abb.c
om/Vtrin
The progid value is just some name that can be used if multiple
connections to the same OPC UA server is wanted to be configured. If
the ProgId is present, the SID name for the connection is
nodename_port_progid. If ProgId is not present, the SID name is just
nodename_port. (The SID name is just an identifying name for the
server connection in the RTDB OPC client. The SID name is present in
the diagnostic messages, and also in the name of the Item Report file
("EcOpcClient-ItemReport-sid.txt"). The DaPath has also space for a
class id name after the progid. The class id should be left as
empty.The namespace definition can be omitted if a default has been
defined in SimpleConfig setting AppName/SID_sid as
"NameSpace=name".
For example:
insert into SimpleConfig(SectionName,KeyName,StrValue)
values('RTDB-EcOpcClient', 'SID_fi8-main_4841',
'UaNamespace=http://fi.abb.com/Vtrin')
Check box to indicate if the data is to be collected from Redundant DA
Server Source. By default, this check box will not be selected. If this
check box is selected, then provide the path details in the Path field.
Provide the Frequency (or Update Rate) for this tag to be read by the
History DA Client. By default, the value for this field will be 1000 ms.
Field to indicate if deadband needs to be applied for the tag. By
default, the value for this field is 0.
Section 3 Engineering and Configuration
Description
2PAA107563-600 B

Hide quick links: