Events not Appearing in 800xA History Embedded Data Collector
Events not Appearing in 800xA History Embedded Data
Collector
In 800xA Workplace, verify the 800xAHistoryEventCollector service is in Service
mode and the Connection String is: tcp://127.0.0.1:7614/CPIMS-
INTERNAL/<Node-Name>-RTDB and appropriate Username/Password are entered.
Trends not Appearing in 800xA
1.
2.
Logs not Appearing in 800xA
In 800xA History Embedded Data Collector Node, select any log configuration in
control structure and check that you are able to get log values. If not, then verify
from Service Control Manager, that 800xA History OPC HDA Server is in "Started"
state. Start HDA server if it is in stopped state.
Redundant 800xA History Embedded Data Collector Node
Following is checked for 800xA History Embedded Data Collector Node
redundancy to work in 800xA:
76
b.
In the pop-up, provide the connection string, username, password
(mentioned above).
c.
Check the connection succeeds and you are able to login to Vtrin GUI.
Check in 800xA History SyncService => Service definition aspect => Special
Configuration tab, Check for HDAProgid, Main Node, IP address of Main
Node are configured correctly.
Also verify Basic History should be running and it should be running on the
same node as that of 800xA History Embedded Data Collector Node.
In 800xA History Embedded Data Collector Node, select any log configuration
in control structure and check that you are able to get log values. If not, then
verify from Service Control Manager, that 800xA History OPC HDA Server is
in "Started" state. Start HDA server if it is in stopped state.