CSV data (apportioned calculation results) [Metering device]
Billing-related sheet
⑨ Check that measurement was able to be carried out successfully (with no errors) during the trial run. If it
was successful, put a check in the check column.
⑩ Extract the CSV data for 1-day intervals for the AE-200 metering device and check the electric energy data
for each unit price. The entry for items with no unit price set will be "0".
(4) Checking the data for the different types of data
⑪ Calculate the totals for each metering device and enter the total value.
• If the pulse weight [kWh] is selected in "Unit Settings" > "PI Controller" and [Outdoor unit] is selected as
the unit type in "Billing Function Settings" > "Measurement" on the Initial Setting Tool, calculate the total in
Total - Outdoor unit (kWh) column. Likewise, if [Indoor unit] is selected as the unit type, calculate the total
in Total - Indoor unit (kWh) column, and if [Other] is selected, calculate the total in Total - Others (kWh)
column.
• If "Pulse weight [MJ]" is selected in "Unit Settings" > "PI Controller", calculate the total in Total - MJ column.
• If "Pulse weight [m3]" is selected in "Unit Settings" > "PI Controller", calculate the total in Total - m3
column.
• If "Pulse weight [--]" is selected in "Unit Settings" > "PI Controller", calculate the total in Total - -- column.
Note
• If [Same power source (O/U - I/U)] is selected as Power source of A-control unit in "Billing Function
Settings" > "Billing Function", the total will be calculated in Total - Outdoor unit (kWh) column.
• If [Separated power source (O/U - I/U)] is selected as Power source of A-control unit in "Billing Function
Settings" > "Billing Function", the totals will be calculated separately in Total - Indoor unit (kWh) and Total -
Outdoor unit (kWh) columns.
WT07442X02
⑨
⑪
110
⑩