Indoor Unit Settings - Mitsubishi Electric AE-200A Instruction Book

Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

6-7-3. Indoor unit settings

Set the cooling capacity, fan power consumption and standby electric power for connected indoor units.
When [Not apportion] is selected in "Indoor unit electric energy apportioning mode" in section 6-7-1 "Billing
function settings", this setting is required.
Procedures
1. Click [Billing Function Settings] > [Indoor Unit] to access the indoor unit settings screen.
Target centralized
controller
Select one of the connected
centralized controllers
whose indoor unit settings
are to be made.
Indoor unit
Displays the indoor units
registered in the refrigerant
system settings.
2. Check that the addresses of the indoor units connected to the controller selected in "Target centralized
controller" are displayed in the "Indoor unit" column.
Note
• The addresses of the indoor units (air conditioners, A-control units, Air To Water (PWFY) units, and
LOSSNAY with heater/humidifier) set as indoor units in section 6-6-2 "Refrigerant System settings", and
the addresses of the LOSSNAY units set in section 6-6-1 "Group settings" will be displayed.
• Make the settings for all the connected indoor units (including LOSSNAY with and without heater/
humidifier).
3. Make the cooling capacity, fan power consumption and standby electric power settings.
The settings can be entered either manually or by referencing the Initial Setting Tool database.
4. After the settings are completed, click [Save].
WT07442X02
Save
Click to save the settings.
88
Cooling capacity
Enter the cooling capacity
for the indoor unit.
Fan power consumption
Enter the fan power
consumption for the indoor
unit.
Unit info.
Click to display the unit
selection screen.
Standby electric power
Enter the standby electric
power for the indoor unit.