6-6-7. AI controller settings

To use temperature and humidity sensors, follow the instructions below to register AI controllers (PAC-YG63MCA)
and to make measurement settings.
Note
• Only the addresses that have not been registered on the group, interlocked LOSSNAY, or PI controller
setting screens are available for selection.
Procedures
1. Click [Unit Settings] > [AI Controller] to access the AI controller settings screen.
Target centralized
controller
Select one of the connected
centralized controllers
whose AI controller settings
are to be made.
AI controller registration
Click to display the screen
for registering AI controllers.
Sensor name
Selection of
temperature or humidity
sensor icon
2. Click the icon in "AI controller registration" (
3. Select the address number of the AI controller to be registered, and click [OK].
4. Enter the name of the sensor in 20 characters or less.
5. Select a temperature sensor icon (
use" can also be selected.
6. Enter the measurable range of the sensor.
When the Pt100 sensor is connected, the range must be between -30ºC (-22ºF) and +60ºC (+140ºF). (Only
Ch1 can be used for the Pt100 sensor.)
When the sensors other than the Pt100 sensors are connected, enter the ranges that are described in the
operation manuals of the sensor.
WT07442X02
Save
Click to save the settings.
Acquire
) to display the unit address selection screen.
) or humidity sensor icon (
82
Measurement setting
Back
Click to display the previous
settings without making any
changes.
Measurable range
Upper/lower ON- and
OFF-threshold settings
for e-mail alarm function
Upper limit
(ON-threshold)
Upper limit
(OFF-threshold)
Lower limit
(OFF-threshold)
Lower limit
(ON-threshold)
) for Ch1 and Ch2 respectively. "Not in