Charge Calculation Tool Settings - Mitsubishi Electric AE-200A Instruction Book

Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

4-1-2. Charge Calculation Tool settings

(1) Metering device connection (Connected/Not connected)
Set whether or not a metering device (the PI controller connected with the electricity meter used for the
apportioned electricity billing function) is connected. When [Not connected] is selected, the charge rate [%]
will be output instead of the apportioned electric energy [kWh].
Important
• When multiple AE-200 units are connected, make the same [Use]/[Non-use] setting on the [Billing Function
Settings] > "Apportioning with metering device" screen on each AE-200 unit (Initial Setting Tool).
If the settings are not the same, the following error message will appear:
"Metering device connection settings (connection or non-connection) on the Charge Calculation Tool
and the AE-200 do not match. Check the [Metering device connection] setting on the Advanced Settings
screen, and check for proper AE-200 billing function settings."
(2) Calculation of standby electric energy (Include in the charges/Not include in the charges)
Make the setting whether to include the standby electric energy for indoor units or outdoor units in the invoice
issued to the tenant.
This setting is not required in systems where the electric energy is entered manually (no-metering-device
method).
Procedures
1. Select [Include in the charges] or [Not include in the charges].
Note
• Refer to section 6-7-1 "Billing function settings" for how to apportion the standby electric energy and the
invoice.
(3) Currency unit
Procedures
1. Set a currency unit.
* The total charge for each energy management block (tenant) per unit price will be rounded down to the specified number of decimal
places or less. (Between 0 and 4 decimal places can be specified.)
For example, if "2 decimal places" is specified and the calculation result is $123.456, the charge will be $123.45.
(4) Display order of charge calculation result (Number/Name), Merger of energy management
blocks with same name (Merge/Not merge)
Make the setting for the output (printout and CSV file) order.
1) Display order of charge calculation result
Procedures
1. Select [Number] or [Name].
The display order of the energy management block names in the charge calculation result will be changed.
• If "Number" is selected, it will be displayed in order of the energy management block numbers set on the
Initial Setting Tool.
• If "Name" is selected, it will be displayed in order of the energy management block names.
WT07442X02