results) output from the AE-200.
For example, when the CSV data (apportioned results) acquired on the LCD runs from April 1, 2015 to
April 30, 2015, the Charge Calculation Tool cannot calculate charges for CSV data outside that range (e.g.
March 20, 2015 to April 19, 2015). Consequently, it is recommended that you specify the maximum date
range (the previous 62 days) for CSV data (apportioned results) output.
• Refer to section 4-2 "Calculating the charges for 2 months ago or earlier" to calculate charges for data
more than 62 days (2 months) previously.
[2] Systems where the electric energy is entered manually (no-metering-device method)
Even when no electricity meters are connected, the charge rate can still be calculated by using "Energy
management block" data.
Procedures
1.-3. Refer to section [1] "CSV files (apportioned results) in systems where electric energy is metered (with-
metering-device method)".
4. Touch [CSV output] to display the CSV output screen and then follow the steps ① to ③ .
① Data to be output
• Select [Energy management block].
② Data type
• Select [1-day intervals].
③ Data-acquisition period
• Touch [Date range] and select the previous 62 days as the range.
5. Touch [CSV output].
Note
• To calculate the charges, be sure to select [1-day intervals].
(Do not select [1-month intervals] or [30-minute intervals].)
• The AE-200 holds the data for the previous 62 days in 1-day intervals.
• The Charge Calculation Tool can calculate charges within the date range of the CSV data (apportioned
results) output from the AE-200.
For example, when the CSV data (apportioned results) acquired on the LCD runs from April 1, 2015 to
April 30, 2015, the Charge Calculation Tool cannot calculate charges for CSV data outside that range (e.g.
March 20, 2015 to April 19, 2015). Consequently, it is recommended that you specify the maximum date
range (the previous 62 days) for CSV data (apportioned results) output.
• Refer to section 4-2 "Calculating the charges for 2 months ago or earlier" to calculate charges for data
more than 62 days (2 months) previously.