108
Action
Close the main contactors (option +F250] or the main breaker [Q1]
(option +F255), and start the DSU: Turn the three-position operating
switch [S11] on the cabinet door from 0 to the START position for 2 s.

Setting up the supply unit control program

Check the settings of the supply unit control program.

Setting up the drive application program

Select the application macro and adjust the parameter settings of the
drive application program to meet the application needs.

On-load checks

Check the correct operation of the emergency stop circuits from each
operating location.
If the drive is equipped with the category 1 emergency stop function
(option +Q952 or +Q964), adjust the delay time of the emergency stop
relay and the deceleration time of the drive emergency stop function.
The factory default settings do not necessarily meet the application
needs.
Check that the Prevention of unexpected start-up function from each
operating location.
Check the correct operation of the Safe torque off function from each
operating location.
Activate and check the operation of the power loss ride-through function.
if automatic restart is required/allowed after a short power supply break.
If the earth fault monitoring is used, check its settings.
Check that the cooling fans rotate freely in the right direction, and the air
flows upwards.
Check the direction of rotation of the motor.
Installation checklist and start-up
Additional information
See section Start-up in ACS800
diode supply control program
firmware manual
(3AUA0000068937[English]).
Appropriate Firmware Manual of the
drive application program delivered
with the drive.
Optional device (options +Q951,
+Q952, +Q963, +Q964). See
delivery specific circuit diagrams and
Safety options instructions for
ACS800 drives (3AUA0000026238
[English]).
Optional function (+Q950). See
delivery specific circuit diagrams and
Safety options instructions for
ACS800 drives (3AUA0000026238
[English]).
Optional function (options +Q967,
+Q968). See delivery specific circuit
diagrams and Safety options
instructions for ACS800 drives
(3AUA0000026238 [English]).
See ACS800 diode supply control
program firmware manual
(3AUA0000068937[English]).
Optional device (option +Q954). See
the documentation of the monitoring
device delivered with the drive or
from www.bender.org.
Check visually that the fans rotate in
the direction indicated by an arrow
on the fan housing.