48

Holes inside the cabinet

The cabinet can be fastened to the floor using the fastening holes inside the cabinet,
if they are accessible. The recommended maximum distance between the fastening
points is 800 mm (31.5").
If there is not enough working space behind the cabinet for mounting, replace the
lifting lugs at the top with L-brackets (not included) and fasten the top of the cabinet
to the wall.
Distances between fastening holes
Bolt size: M10 to M12 (3/8" to 1/2").
Cubicle
Distance between holes
Width
300
400
600
700
800
Mechanical installation
Outer
Ø31 mm (1.22")
150 mm (5.9")
250 (9.85")
450 (17.7")
550 (21.65")
650 (25.6")
Fastening holes inside the
cabinet (marked with arrows)
Fastening the cabinet at the top with
L-brackets (side view)
Added width:
Side panels of the cabinet: 15 mm (0.6")
Back panel of the cabinet: 10 mm (0.4")
Gap between cubicles (mm):
IP 20 ... 42
(0.02")
L-bracket
M16 screw
Cabinet top
IP 54
0.5
1
(0.04")