Connections And Tap Settings Of The Auxiliary Voltage Transformer Of The Drive - ABB ACS800 Hardware Manual

Acs800-07 (+v992) drives (500 to 2800 kw)
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

96
Connections and tap settings of the auxiliary voltage transformer
of the drive
Supply
Terminals
voltage
690 V
A1, B1, C1
660 V
A1, B1, C1
600 V
A1, B1, C1
575 V
A1, B1, C1
525 V
A1, B1, C1
500 V
A1, B1, C1
480 V
A1, B1, C1
460 V
A1, B1, C1
440 V
A1, B1, C1
415 V
A1, B1, C1
400 V
A1, B1, C1
380 V
A1, B1, C1
Electrical installation
Output
3~ input
Tap settings
A1 to... B1 to... C1 to...
C2
A2
B2
C2
A2
B2
C3
A3
B3
C3
A3
B3
C4
A4
B4
C4
A4
B4
C5
A5
B5
C5
A5
B5
C6
A6
B6
C6
A6
B6
C7
A7
B7
C7
A7
B7
3~ Input
1~ output
230 V
Supply
voltage
Terminals
Tap setting
690 V
a3, n1
230–
660 V
a3, n1
230+
600 V
a3, n1
230–
575 V
a3, n1
230+
525 V
a3, n1
230–
500 V
a3, n1
230+
480 V
a3, n1
230–
460 V
a3, n1
230+
440 V
a3, n1
230–
415 V
a3, n1
230+
400 V
a3, n1
230–
380 V
a3, n1
230+
3~ output
400 V (50 Hz)
320 V (60 Hz)
Terminals
Terminals
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2
a1, b1, c1
a2, b2, c2