Alternative Power Cable Types; Motor Cable Shield; Additional Us Requirements - ABB ACS800 Hardware Manual

Acs800-07 (+v992) drives (500 to 2800 kw)
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Alternative power cable types

Power cable types that can be used with the drive are represented below.
Recommended
Symmetrical shielded cable: three phase conductors
and a concentric or otherwise symmetrically
constructed PE conductor, and a shield
PE conductor
and shield
A four-conductor system:
three phase conductors
and a protective
conductor.

Motor cable shield

To effectively suppress radiated and conducted radio-frequency emissions, the
shield conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminium shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires with an open helix of copper tape. The better and
tighter the shield, the lower the emission level and the bearing currents.

Additional US requirements

Type MC continuous corrugated aluminum armor cable with symmetrical grounds or
shielded power cable must be used for the motor cables if metallic conduit is not
used. For the North American market, 600 VAC cable is accepted for up to 500 VAC.
1000 VAC cable is required above 500 VAC (below 600 VAC). For drives rated over
100 amperes, the power cables must be rated for 75
Shield
PE
PE
Not allowed for motor cables
Copper wire screen
Insulation jacket
A separate PE conductor is required if the conductivity
of the cable shield is < 50 % of the conductivity of the
phase conductor.
Not allowed for motor cables with phase
conductor cross section larger than 10 mm
(motors > 30 kW).
Helix of copper tape
°
C (167
Planning the electrical installation
Shield
PE
Shield
2
Inner insulation
Cable core
°
F).
67