ABB COM600 Series User Manual page 47

Dnp 3.0 serial master (opc) substation management unit
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

1MRS756567
COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Net Multiplier
Default: Deka
Net Scale
Default: None
Net Unit
Default: Dimensionless
Net Number of
0 to 9
Decimals
Res Multiplier
Default: Deka
Res Scale
Default: None
Res Unit
Default: Dimensionless
Res Number of
0 to 9
Decimals
Phase Limit Value
Supervision
Max
Default: 20000
Min
Default: 0
Neutral Limit Value
Supervision
Max
Default: 20000
Min
Default: 0
Table 3.4.8.18-2 Additional configurable properties for Sub-Type WYE Full
Property/ Para-
Value or Value range/ Default
meter
Sub-Type
WYE Full
Phase Limit Value
Supervision
High
Default: 0
High-High
Default: 0
Low
Default: 0
Low-Low
Default: 0
Neutral Limit Value
Supervision
High
Default: 0
Description
Specifies the multiplier for the current SI
unit.
Scale for Net used with this data object.
Unit for Net.
Specified the number of decimals shown
in HSI.
Specifies the multiplier for the current SI
unit.
Scale for Res used with this data object.
Unit for Res.
Specified the number of decimals shown
in HSI.
Maximum value for measurement.
Minimum value for measurement.
Maximum value for measurement.
Minimum value for measurement.
Description
Subtype of WYE.
High limit for measurement. Event is cre-
ated when value crosses the limit.
High-high limit for measurement. Event is
created when value crosses the limit.
Low limit for measurement. Event is cre-
ated when value crosses the limit.
Low-low limit for measurement. Event is
created when value crosses the limit.
High limit for measurement. Event is cre-
ated when value crosses the limit.
47