Binary Controlled Step Position Information; Bsc; Complex Measured Value (Cmv) - ABB COM600 Series User Manual

Dnp 3.0 serial master (opc) substation management unit
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

3.4.8.6.
3.4.8.7.
34
COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual
Binary controlled step position information (BSC)
Table 3.4.8.6-1 Configurable BSC properties
Property/ Parameter
Value or Value range/
Default
Basic
Common Data Class

BSC

Addresses
Control Index
-1 to 65535
Default: -1
Indication Index
-1 to 65535
Default: -1
Data Class Specific
Control Code Qualifier
Momentary
Latched
Pulsed
Default: Momentary
Control Variation
0 to 65535
Operate
Direct Operate
Select Before Operate
Default: Direct Operate
Scale and Unit
Scale
Default: None

Complex measured value (CMV)

Table 3.4.8.7-1 Configurable CMV properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
CMV
Class
Addresses
Index
-1 to 65535
Default: -1
Description
Common data class according to IEC 61850.
Control index.
Indication index.
Qualifier for control.
Variation for control
Specifies using two-step, select-before-operate
method for issuing control request or not.
Scale used with this type.
Description
Common data class according to IEC
61850.
Indication index.
1MRS756567

Advertisement