CHAPTER 4: SETPOINTS
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
the FlexLogic operands are stored in a non-volatile memory. Should the power supply be
lost, the correct state of the pushbutton is retained upon subsequent power-up of the
relay.
ID TEXT
Range: Up to 13 alphanumeric characters
Default: Start (PB1), Stop (PB2), F1 (PB3), Gnd Trip Enabled (PB4), SCADA Enabled (PB5), Hot
Line Tag (PB6), Demand Reset (PB7), Alt Settings (PB8), Target Reset (PB9), PB Block (PB10)
This setting specifies the 13-character line of the user-programmable message and is
intended to provide the ID information of the pushbutton.
ON TEXT
Range: Up to 13 alphanumeric characters
Default: PB1 On (or PB[X] On)
This setting specifies the 13-character line of the user-programmable message and is
displayed when the pushbutton is in the "ON" position. Refer to the Working with
Graphical Display Pages section for instructions on entering alphanumeric characters
from the keypad.
OFF TEXT
Range: Up to 13 alphanumeric characters
Default: PB1 Off (or PB[X] On)
This setting specifies the 13-character line of the user-programmable message and is
displayed when the pushbutton is activated from the "ON" to the "OFF" position and the
PUSHBUTTON 1 FUNCTION is "Latched". This message is not displayed when the
PUSHBUTTON 1 FUNCTION is "Self-reset" as the pushbutton operand status is implied to
be "OFF" upon its release. The length of the "OFF" message is configured with the
PRODUCT SETUP/DISPLAY PROPERTIES/FLASH MESSAGE TIME setting.
The message programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT settings will be
displayed as long as PUSHBUTTON 1 ON operand is asserted, but not longer than the
time period specified by the FLASH MESSAGE TIME setting. After the flash time has
expired, the default message or other active target message is displayed. The
instantaneous Reset of the flash message will be executed if any relay front panel
button is pressed or if any new target or message becomes active.
The PUSHBTN 1 OFF TEXT setting is linked to PUSHBUTTON 1 OFF operand and will be
displayed in conjunction with PUSHBTN 1 ID only if the pushbutton element is in
"Latched" mode.
HOLD PRESSED
Range: 0.0 to 10.0 s in steps of 0.1 s
Default: 0.1 s
This setting specifies the time required for a pushbutton to be pressed before it is
deemed active.
The timer is Reset upon release of the pushbutton. Note that any pushbutton operation
will require the pushbutton to be pressed a minimum of 60 ms. This minimum time is
required prior to activating the pushbutton hold timer.
AUTORESET
Range: Disabled, Enabled
Default: Disabled
This setting enables the user-programmable pushbutton Autoreset feature. The setting
is applicable only if the pushbutton is in "Latched" mode.