GE 869 Instruction Manual page 188

Motor protection system
Hide thumbs Also See for 869:
Table of Contents

Advertisement

DEVICE
4–56
AUTORESET DELAY
Range: 0.2 to 600.0 s in steps of 0.1 s
Default: 1.0 s
This setting specifies the time delay for automatic Reset of the pushbutton when in the
"Latched" mode.
LOCK
Range: Off, Any FlexLogic operand
Default: Off
This setting assigns a FlexLogic operand serving to inhibit pushbutton operation from
the front panel pushbuttons. This locking functionality is not applicable to pushbutton
autoreset.
DROPOUT TIME
Range: 0.0 to 600.0 s in steps of 0.1 s
Default: 0.0 s
This setting applies only to "Self-reset" mode and specifies the duration of the
pushbutton "active" status after the pushbutton has been released. The length of time
the operand remains on has no effect on the pulse duration.
The setting is required to set the duration of the pushbutton operating pulse.
EVENTS
Range: Disabled, Enabled
Default: Enabled
Table 4-18: PB1 to PB3 Default Values (Membrane and Rugged Front Panels)
Function
ID Text
ON Text
OFF Text
LED Trigger
Hold Pressed
Autoreset
Autoreset Delay
Lock
Dropout Time
Events
PB1
PB2
Self-Reset
Self-Reset
Start
Stop
PB1 ON
PB2 ON
PB1 OFF
PB2 OFF
PB1 ON
PB2 ON
0.1s
0.1s
Disabled
Disabled
1.0s
1.0s
Off
Off
0.0s
0.0s
Enabled
Enabled
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS
PB3
Self-Reset
F1
PB3 ON
PB3 OFF
PB3 ON
0.1s
Disabled
1.0s
Off
0.0s
Enabled