MONITORING
4–284
Figure 4-116: Fault indicating frequencies are highlighted
11. If the change in dB of peak and energy magnitude is greater than the pick up levels
configured in the ESA set points, then a corresponding fault element will be triggered
after the configured delay only if the level is sustained.
12. The dBs can be visualized in the form of a circle under the path Motor M&D\Bala's
Circle to know the motor status (normal, caution or alarm) as represented in the
following figure.
Figure 4-117: Motor status visually represented in circular format
A circle is drawn with 3 dBs taken into consideration – baseline dB corresponding
to 'k' value where maximum change in dB is observed, PKP level 1 dB setting and
PKP level 2 dB setting as the radius of circles corresponding to the baseline,
caution and alarm zones.
The entire circle is divided into 12 equal sections covering 30 degrees of
circumference corresponding to each load bin. Load bin 1 starts at 0 degrees and
ends with load bin 12 at the 360 degree point in the anti-clockwise direction.
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS