CHAPTER 4: SETPOINTS
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MODE
Range: Definite Time, Adaptive
Default: Definite Time
The setting defines the operating mode of the Acceleration Time element. When set to
"Definite Time", the element times duration of the motor start and operates when the
starting time exceeds the acceleration Time setting. When set to "Adaptive", the element
uses the effective accelerating current to adapt to the starting conditions. The operating
equation assumes that the accelerating power is proportional to the square of the
current and neglects any current unbalance or impact of the rotor slip. Consequently, in
the Adaptive mode, the element operates when the square of the current integrated
from the beginning of the start up to a given time exceeds the product of acceleration
2
Current
x Time.
OUTPUT RELAY X
For details see
Common
BLOCK
Range: FlexLogic Operand
Defatul: Off
The Acceleration Time element can be blocked by any asserted FlexLogic operand.
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Disabled
Default: Latched
Setpoints.
PROTECTION
4–165