GE 869 Instruction Manual page 39

Motor protection system
Hide thumbs Also See for 869:
Table of Contents

Advertisement

CHAPTER 1: INTRODUCTION
FASTPATH:
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
TRIP/CLOSE OUTPUT RELAYS
(Relays #1 and #2 from Slot F, Relays #9 and #10 from Slot G)
Type: .........................................................................FORM-A
Configuration:.......................................................2 (two) electromechanical
Contact material: ................................................silver-alloy
Operate time:........................................................<8 ms
Continuous current:...........................................10 A
Make and carry for 0.2s:..................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
Break (DC resistive):............................................24 V / 10 A
Break (AC inductive): ..........................................720 VA @ 250 VAC Pilot duty A300
Break (AC resistive): ............................................277 VAC / 10 A
Operation Mode:..................................................Self-Reset, Latched, Pulsed, Non-Failsafe, Failsafe
FORM-A VOLTAGE MONITOR
Applicable voltage:.............................................20 to 250 VDC
Trickle current:......................................................1 to 2.5 mA
Timer acurracy: ...................................................± 3% of operate time or ± 1/4 cycle (whichever is greater)
AUXILIARY OUTPUT RELAYS
(Relays #3, #4 and the Critical Failure Relay from Slot F, and Relays #11, #12 and #16 from
Slot G)
Type: .........................................................................FORM-C
Configuration:.......................................................electromechanical
Contact material: ................................................silver-alloy
Operate time:........................................................<8 ms
Continuous current:...........................................10 A
Make and carry for 0.2s:..................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
Break (DC resistive):............................................24 V / 10 A
Break (AC inductive): ..........................................720 VA @ 250 VAC Pilot duty A300
Break (AC resistive): ............................................277 VAC / 10 A
Operation Mode:..................................................Self-Reset, Latched, Pulsed, Non-Failsafe, Failsafe
Breaking Capacity:.............................................For Form-C relays the following ratings are applied to meet
For 2 IO_A module configuration the following ratings are applied to meet UL508
requirements: 1 second "on"/ 10 seconds "off" per output relay at max rating.
PULSED OUTPUTS
Mode:........................................................................3-phase positive and negative active energy measurement,
Principle:..................................................................Pulsed output is energized for one second and then de-
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
UL508 requirements: 1 second "ON"/10 seconds "OFF" per
output relay at maximum rating
3-phase positive and negative reactive energy
measurements
energized for one second after the programed energy
increment.
SPECIFICATIONS
1–29