Mitsubishi Electric Q01UCPU User Manual page 359

Hide thumbs Also See for Q01UCPU:
Table of Contents

Advertisement

(3)
Low-speed timer
This type of timer measures time in increments of 1 to 1000ms.
The timer starts time measurement when its coil is turned on, and when it times out, the contact is turned on. If
the timer's coil is turned off, the current value is changed to "0" and the contact is turned off.
[Ladder example]
X0
[Timing chart]
X0
OFF
T0 coil
OFF
T0 contact
OFF
(a) time increment setting
The time increment is set in the PLC system tab of the PLC parameter dialog box.
The default is 100ms, and it can be changed in increments of 1ms.
(4)
High-speed timer
This type of timer measures time in increments of 0.01 to 100ms.
The timer starts time measurement when its coil is turned on, and when it times out, the contact is turned on. If the
timer's coil is turned off, the current value is changed to "0" and the contact is turned off.
[Ladder example]
X0
[Timing chart]
X0
OFF
T200 coil
OFF
T200 contact
OFF
(a)
setting
Time increment
The time increment is set in the PLC system tab of the PLC parameter dialog box.
The default is 10.0ms, and it can be changed in increments of 0.01ms.
K10
When X0 is turned on, coil of T0 is turned on, and the
T0
contact turns on after 1s. (when unit of the timer is set
to 100ms)
ON
ON
1s
ON
Enter a value.
High-speed timer
H
K50
When X0 is turned on, coil of T200 is turned on, and the
contact turns on after 0.5s. (when unit of the timer is set
T200
to 10ms)
ON
ON
0.5s
ON
Enter a value.
CHAPTER 4 DEVICES
4
357